Modbus Output Port Registers
Refer to the following two tables to configure the Power Patrol output ports when using the Modbus
protocol.
Port 1 output control
when used as an on/off—
open/closed switch
0 = output LOW (closed)
1 = output HIGH (open) [default]
Register 45110 must = 0 to use
Digital Port 1
Configuration
Turns pulses on/off
0 = No pulses, Port may be used as an
on/off—
open/closed switch
44001 = System kWh pulses
44008 = System kVARh pulses
44011 = System kVAh pulses
Port 1 pulse output relay
type
0 = normally open (HIGH)
1 = normally closed (LOW)
Table C-2: Modbus Digital Port Pulse Output
BACnet Output Port Objects
Refer to the following two tables to configure the Power Patrol output ports when using the BACnet
protocol.
Port 1 output control when used as an
on/off—open/closed switch
0 = output LOW (closed) 1 = output HIGH
(open) [default]
Object 13100 present value must = 0 to use
Digital Port 1 Configuration
Turns pulses on/off
0 = No pulses, Port may be used as an
on/off—
open/closed switch
44001 = System kWh pulses
44008 = System kVARh pulses
44011 = System kVAh pulses
Port 1 pulse output relay type
0 = normally open (HIGH)
1 = normally closed (LOW)
Table C-3: BACnet Digital Port 1 Pulse Output