Multiply volts values by this scalar. Use with Step-
down Transformer. Affects all parameters that use
volts (i.e., kW)
Multiply amps value by this scalar. For use with x:5A
CTs and single let monitoring of a three phase load.
Affects all parameters that use amps (i.e, kW)
A value of 0x0001 configures the meter for DELTA
A value of 0x0000 configures the meter for WYE
Line frequency setting for metering: 50=50 Hz,
60=60Hz
Write 1833 to change to BACnet mode
Fractional part of NV_CT1
Select 1=mV or 2=Rogowski CT1s
Fractional part of NV_CT2
Select 1=mV or 2=Rogowski CT2s
Fractional part of NV_CT3
Select 1=mV or 2=Rogowski CT3s
PULSE OUTPUT/INPUT REGISTERS
Port 1 output control when
used as an on/off—open/closed
switch
0 = output LOW (closed)
1 = output HIGH (open) [default]
Register 45110 must = 0 to use
Digital Port 1 Configuration
Turns pulses on/off
0 = No pulses, Port may be used as an on/off—
open/closed switch
44001 = System kWh pulses
44008 = System kVARh pulses