INTRODUCTION
The Power Patrol meter monitors the voltage, current, power, energy, and many other electrical
parameters on single- and three-phase electrical systems. A Power Patrol meter uses direct connections
to each phase of the voltage, and uses current transformers or Rogowski coils to monitor each phase of
the current. Information on energy use, demand, power factor, line frequency, and more are derived
from the voltage and current inputs.
The communications interface to the meter is an USB communication, or RS-485 serial/Ethernet
connection that uses the BACnet Master Slave Token Passing (MS/TP) protocol or Modbus protocol for
sending commands and retrieving data. A separate remote terminal unit (RTU), Data Logger, or Building
Management and Control System is usually connected to the Power Patrol to provide data recording
and trend logging plus a human interface or display.
POWER PATROL
The Power Patrol is light-weight and compact enough to
mount within an electrical panel. It is typically used for
long-term monitoring of electrical systems.
Up to 127 Power Patrol meters may be connected to a
single BACnet client for monitoring and recording power
usage at multiple locations within a single site. Up to 247
meters may be connected to Modbus.
There is a configurable digital pulse output port on the
Power Patrol that can be used to output kWh, kVARh, or kVAh pulses to external devices, or to toggle on
and off to control a remote device or relay.
Power Patrol Meter Safety Summary and Specifications
This general safety information is to
be used by both the Power Meter
operator and servicing personnel.
Setra Systems, Inc. assumes no
liability for user’s failure to comply
with these safety guidelines.
PS3037-X-X
These items conform to the
following:
Conforms to UL Std 61010-1, 3rd
Edition & IEC 61010-2-030, 1
st
Edition
Certified to CSA Std C22.2 No.
61010-1, 3rd Edition
The Power Patrol is an over-voltage Category III device. Use approved rubber gloves with mechanical protection and
goggles when operating the device.